E. Test for spitlage atthe draft hood retief opening
after 5 minutes of main burner operation. Use
the flame of a match or candle, or smoke from
a cigarette, cigar or pipe.
F. After it has been determined that each appli-
ance remaining connected to a common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning
appliances to their previous condition of use.
G. Any improper operation of the common vent-
ing system should be corrected so the installation
conforms with the latest revision of the National
Fuel Gas Code, ANSI Z223.1. When resizing
any portion of the common venting system, the
common venting system should be resized to
approach the minimum size as determined us-
ing the appropriate tables in appendix G in the
latest revision of the National Fuel Gas Code,
ANSI Z223.
NOTE: Refer to Figure 11 for steps 1-7.
!NSTALL R
HOOK JP
DAMPR
,MOTOR
VENT
DAM_'ER
VENT
OI.TLET
INSTALL R
OOK U?
/"
CONTROL
VENT DAMPER
HAR ESS
H! LIM,F _'_
CONTROL
I FIGURE 111
FACTORY WRD
1. Place Vent Damper on or as close to vent outlet
of boiler as possible. (Figure 12)
2. Remove Vent Damper Motor cover.
3. Remove Iocknut from connector at the end of the
Damper wire harness.
4. Feed Damper and Damperwire harness connectors
through bracket hole on Damper Motor frame.
5. Replace and tighten Iocknut onto Damper wire
harness connector.
6. Plug Damper connector into socket on Damper
Motor frame.
7. Replace Damper Motor cover and wire Damper
in accordance with Figure 11.
1. Ensure that only the boiler is serviced by the Vent
Damper. (Figure 12)
LJIX #C:C:EPT,_ BLE
E)#I PER LOC#T ONS
HOT d'/ATER HEATER
IFIGURE 121
2. Clearance of not less than 6 inches between Vent
Damper and combustible material must be main-
tained. Additional clearance should be allowed for
service of Vent Damper.
3. Vent Damper must be in the open position when
appliance main burners are operating.
4. The Vent Damper position indicator must be in a
visible location following installation.
5. The thermostat's heat anticipator must be adjusted
to match the total current draw of all controls associ-
ated with the boiler during a heating cycle.