P/N# 240009276, Rev. A [03/2012]
RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE
These instructions must be af xed on
or adjacent to the boiler.
GAS FIRED BOILER
INSTALLATION
INSTRUCTIONS
PRODUCT LITERATURE
Lennox Industries Inc.
Dallas, Texas
This boiler cannot be used with all types of
chimneys. Read these instructions carefully
before installing.
GAS-FIRED HOT WATER BOILERS
These Gas-Fired Water boilers are low pressure,
sectional cast iron boilers Design Certi ed by
CSA (Canadian Standards Association) for
use with Natural and Propane Gases. They
are constructed and hydrostatically tested for
maximum working pressure of 50 psi (pounds
per square inch) in accordance with A.S.M.E.
(American Society of Mechanical Engineers)
Boiler and Pressure Vessel Code Section IV
Standards for Cast Iron Heating Boilers.
Tested for 50 psi. ASME
Working Pressure
C.S.A. Certi ed for
Natural gas or Propane
WARNING
Improper installation, adjustment,
alteration, service, or maintenance
can cause injury or property damage.
Refer to this manual. For assistance
or additional information consult a
quali ed installer, service agency, or
the gas supplier.
!
GWB8-262E-2
GWB8-245E-2
GWB8-299E-2
GWB8-280E-2
Page view 0
1 2 3 4 5 6 ... 31 32

Summary of Contents

Page 1 - INSTRUCTIONS

P/N# 240009276, Rev. A [03/2012]RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCEThese instructions must be affi xed on or adjacent to the boiler.GAS FI

Page 2 - Table 1 - Dimensions

10Figure 6 - BYPASS PIPING - CIRCULATOR ON SUPPLYFigure 7 - BYPASS PIPING - CIRCULATOR ON RETURNBypass Piping Required For High Mass (Large Water Cont

Page 3

11Boilers connecting to gas vents or chimneys, vent installations shall be in accordance with “Venting of Equipment”, of the National Fuel Gas Code, A

Page 4

12Minimum Vent Pipe ClearanceWood and other combustible materials must not be closer than 6” from any surface of single wall metal vent pipe. Listed T

Page 5 - 18"

138 - VENT DAMPER OPERATIONFigure 8 - Vent Damper Installation Figure 9 - Vent Damper PlacementAnnually check vent damper and all fl ue product carryin

Page 6

149 - GAS SUPPLY PIPINGCAUTIONWHAT TO DO IF YOU SMELL GAS• Do not try to light any appliance.• Do not touch any electrical switch; do not use any phon

Page 7

1510 - ELECTRICAL WIRINGElectrically bond boiler to ground in accordance with requirements of authority having jurisdiction. Refer to:• USA- Na

Page 8

1611 - WIRING DIAGRAMSFigure 12 - Integrated High Limit Electronic Ignition Control (240008781)IInducer is not an option. WARNINGModifi cation, substit

Page 9

1711 - WIRING DIAGRAMSFigure 13 - Integrated High Limit Electronic Ignition Control (240008781)

Page 10

1811 - WIRING DIAGRAMSFigure 14 - Integrated High Limit Electronic Ignition Control (240008781)

Page 11 - WARNING

1912 -GENERAL INSTRUCTIONSFILLING SYSTEM WITH WATER• Close air vents on all radiation units. Open valves to these units. • Verify boiler and expansion

Page 12

21 - DIMENSIONSTable 1 - DimensionsBOILER MODEL NUMBERDIMENSIONS (INCH.)FLUE DIAMETER“A” WIDTHGWB8-245E-2/GWB8-262E-2727½GWB8-280E-2/GWB8-299E-27 30¾A

Page 13 - 8 - VENT DAMPER OPERATION

2013 - LIGHTING INSTRUCTIONS1. STOP! Read the safety information above. 2. Set the thermostat to lowest setting.3. Turn off all electric power to the

Page 14 - WHAT TO DO IF YOU SMELL GAS

2114 - OPERATING YOUR BOILERAUTOMATIC GAS VALVEAutomatic Gas Valve opens or closes according to heat requirements of thermostat and temperature limit

Page 15

2214 - OPERATING YOUR BOILERCHECK THERMOSTAT OPERATIONA. When set above temperature indicated on thermostat, boiler should ignite. B. Verify thermost

Page 16

2315 - MAINTAINING YOUR BOILERBURNERSBeginning of heating season visually check pilot and main burner fl ames. See Figure 16.SAFETY RELIEF VALVERefer t

Page 17 - 11 - WIRING DIAGRAMS

24EQUIPMENT AND OPTIONAL ACCESSORIES - WHAT THEY DO16 - SERVICE HINTSYou may avoid inconvenience and service calls by checking these points before you

Page 18

2517 - EQUIPMENT AND OPTIONAL ACCESSORIES EXPANSION TANKExpanding water fl ows into expansion tank. Tank should be correct size. Tank is fi lled with ai

Page 19 - 12 -GENERAL INSTRUCTIONS

26BLOCKED VENT SAFETY SWITCH(BLOCKED VENT SAFETY SHUTOFF)Blocked vent safety switch is manual reset disc thermostat with fi xed setpoint (340°F (171°C)

Page 20

27APPENDIX A - CONTROL MODULEA.1 Installation Environment Considerations WARNINGIf you do not follow these instructions exactly, a fi re or explosion m

Page 21

28APPENDIX A - CONTROL MODULEA.5 OperationModule continuously monitors boiler water temperature and fi res or shuts off burner based on this temperatur

Page 22 - 14 - OPERATING YOUR BOILER

29APPENDIX A - CONTROL MODULEA.6 Boiler High Limit Temperature Controller• When water temperature reaches setpoint, controller ends heating cycle. • W

Page 23 - 15 - MAINTAINING YOUR BOILER

32 - BOILER RATINGS AND CAPACITIES Table 2 - Ratings and CapacitiesBOILER MODEL NUMBER (1)† NATURAL GAS † PROPANE GAS AFUE Input (3) MbhH

Page 24

30APPENDIX A - CONTROL MODULETable 7 - Troubleshooting Error CodesError Code NumberDefi nition Consequence4 Flame current too low. Check for fl ame. Non

Page 25

31APPENDIX A - CONTROL MODULE— If fl ame rod or bracket is bent out of position, restore to correct position.STEP 3: Check spark ignition circuit. Disc

Page 26

PRODUCT LITERATURELennox Industries Inc.Dallas, TexasManufactured by:ECR International, Inc.2201 Dwyer Avenue, Utica NY 13501web site: www.ecrinterna

Page 27

43 - TABLE OF CONTENTSIMPORTANT: Read the following instructions COMPLETELY before installing!!KEEP THIS MANUAL NEAR BOILERRETAIN FOR FUTURE REFERENCE

Page 28

54 - INSTALLATION PROCEDURETable 3 - MINIMUM CLEARANCE DIMENSIONSInches (mm)Top 6” (152mm)Rear 6” (152mm)Control Side 7” (178mm)Opposite Side 6” (152m

Page 29

65 - VENTILATION & COMBUSTION AIRProvide combustion air and ventilation air in accordance with the section “Air for Combustion and Ventilation,” o

Page 30 - APPENDIX A - CONTROL MODULE

76 - CONNECTING SUPPLY AND RETURN PIPINGRELIEF VALVEDISCHARGE LINECheck local codes for maximum distance from fl oor or allowable safe point of dischar

Page 31

86 - CONNECTING SUPPLY AND RETURN PIPING WARNINGBurn and scald hazard. Safety relief valve could discharge steam or hot water during operation. In-

Page 32 - Dallas, Texas

9Figure 5 - Chilled Water PipingFigure 4 - Typical Hot Water Piping6 - CONNECTING SUPPLY AND RETURN PIPING